Check
SiEN12-710A
150
Service Diagnosis
5.1.6 Installation Condition Check
Check No.07
Normal
(R7157)
Abnormal
YES
YES
YES
NO
NO
NO
Change the position of the air
discharge grille or the
installation location.
Change the position of the air
discharge grille or the
installation location.
Change the installation
location or direction.
Check the outside air
temperature (temperature of air
taken in by the outdoor unit).
(The outside air temperature
shall be 46°C or lower.)
Clean the heat exchanger.
Is the heat exchanger
very dirty?
Check the
allowable dimensions
of the air suction and discharge
area.
Is the air
flow blocked by
obstacles or winds blowing in
the opposite
direction?
Does
the discharged
air from other outdoor
unit cause an increase of the
suction air
temperature?
Installation condition check