Main Functions
SiEN12-710A
30
Function and Control
1.6 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
$
The temperature difference is in the zone A.
Thermostat ON Condition
$
The temperature difference is above the zone C after being in the zone A.
$
The system resumes from defrost control in any zones except A.
$
The operation turns on in any zones except A.
$
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
$
Wall Mounted Type
$
Duct Connected Type
Heating
$
Wall Mounted Type
$
Duct Connected Type
B
A
OFF
OFF
ON
ON
C
Room temperature - setpoint
(R4668)
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
Cooling : – 0.5°C
Dry : – 0.5°C
B
B
A
A
OFF
OFF
ON
ON
C
C
– 1.5°C
Room temperature - setpoint
(R6032)
Cooling : – 1.0°C
Dry : – 1.0°C
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
B
B
A
A
OFF
OFF
ON
ON
C
C
1.5°C
Room temperature - setpoint
0°C
(R4669)
B
A
OFF
OFF
ON
ON
C
1.5°C
1.0°C
Room temperature - setpoint
0.5°C
(R6033)
Summary of Contents for 2MKS40FV1B
Page 11: ...Introduction SiEN12 710A x ...
Page 12: ...SiEN12 710A List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Page 17: ...Heat Pump SiEN12 710A 6 List of Functions ...
Page 25: ...Heat Pump SiEN12 710A 14 Specifications ...
Page 111: ...Instruction SiEN12 710A 100 Operation Manual ...
Page 199: ...Wiring Diagrams SiEN12 710A 188 Appendix ...
Page 203: ...SiEN12 710A iv Index ...