Troubleshooting
SiEN12-710A
128
Service Diagnosis
4.15 Position Sensor Abnormality
Remote Control
Display
H6
Method of
Malfunction
Detection
A compressor startup failure is detected by checking the compressor running condition through
the position detection circuit.
Malfunction
Decision
Conditions
"
The compressor is not running in about 15 seconds after the compressor run command
signal is sent.
"
Clearing condition: Continuous run for about 11 minutes (normal)
"
The system will be shut down if the error occurs 16 times.
Supposed
Causes
"
Compressor relay cable disconnected
"
Compressor itself defective
"
Outdoor unit PCB defective
"
Stop valve closed
"
Input voltage out of specification