SiBE12-519
Control Specification
Function and Control
57
3.3
Controls at Mode Changing / Start-up
3.3.1
Preheating Operation
Outline
Operate the inverter in the open phase operation with the conditions including the preheating
command from the indoor, the outdoor air temperature and discharge pipe temperature.
Detail
Preheating ON Condition
When outdoor air temperature is below 10.5°C and discharge pipe temperature is below
10.5°C, inverter in open phase operation starts.
OFF Condition
When outdoor air temperature is higher than 12°C or discharge pipe temperature is higher
than 12°C, inverter in open phase operation stops.
3.3.2
Four Way Valve Switching
Outline of
Heating
Operation
Heat Pump Only
During the heating operation current must be conducted and during cooling and defrosting
current must not be conducted. In order to eliminate the switching sound (as the four way valve
coil switches from ON to OFF) when the heating is stopped, the delay switch of the four way
valve must be carried out after the operation stopped.
Detail
The OFF delay of four way valve
Energize the coil for 150 sec after unit operation is stopped.
3.3.3
Four Way Valve Operation Compensation
Outline
Heat Pump Only
At the beginning of the operation as the four way valve is switched, acquire the differential
pressure required for activating the four way valve by having output the operating frequency,
which is more than a certain fixed frequency, for a certain fixed time.
Detail
Staring Conditions
1. When starting compressor for heating.
2. When the operating mode changes from the previous time.
3. When starting compressor for starting defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
5. When starting compressor after operation stop by the cooling / heating mode change-over
malfunction.
Set the lower limit frequency to 68 (model by model) Hz for 70 seconds with the OR conditions
with 1 through 5 above.
3.3.4
3 Minutes Stand-by
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
FCG 3
90
FCG 2
72
FCG 1
62
TCG 1
110
TCG 2
660
TCG 3
90
Summary of Contents for 2MKS40DVMB
Page 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Page 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Page 29: ...Heat Pump SiBE12 519 20 Specifications ...
Page 135: ...Instruction SiBE12 519 126 System Configuration ...
Page 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...