Main Functions
Function and Control
37
1.3
Fan Speed Control
for Indoor Units
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and
Hall IC
control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 138.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Note:
1. During powerful operation, fan rotates at H tap + 50 - 90 rpm.
2. Fan stops during defrost operation.
Automatic Air
Flow Control for
Heating
The following drawing explains the principle for fan speed control for heating:
Automatic Air
Flow Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
Step
Cooling
Heating
Dry mode
LLL
20 · 25 · 35kW class :
670 - 880 rpm
(During powerful operation :
720 - 930 rpm)
LL
SL (Silent)
L
ML
M
MH
H
HH (Powerful)
(R2818)
(R2818)
-1.5˚C
-0.5˚C
-1˚C
-2˚C
L
ML
M
Thermostat
setting
temperature
DC motor: Rotation speed control
AC motor: Phase control
Difference between room
and set temperature
fan speed
(R4593)
+1.5˚C
+0.5˚C
+2˚C
+1˚C
M
ML
L
fan speed
Difference between room
and set temperature
Thermostat
setting
temperature
(R4594)
DC motor: Rotation speed control
AC motor: Phase control
Summary of Contents for 2MKS40DVMB
Page 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Page 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Page 29: ...Heat Pump SiBE12 519 20 Specifications ...
Page 135: ...Instruction SiBE12 519 126 System Configuration ...
Page 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...