Main Functions
SiBE12-519
46
Function and Control
1.11
Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed / setting
temperature will be converted to the following states in a period of twenty minutes.
In case of FTK(X)S20-35D
Ex.) : Powerful operation in cooling mode.
Operation mode
Fan speed
Target set temperature
COOL
H tap + 50 rpm
18°C
DRY
Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
HEAT
H tap + 50 rpm
30°C
FAN
H tap + 50 rpm
—
AUTO
Same as cooling /
heating in Powerful
operation
The target is kept
unchanged
(R4560)
Target temp.
Fan
50rpm
Set temp.
18˚C
Powerful ON
Powerful OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
20min.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. Powerful operation is OFF.
Summary of Contents for 2MKS40DVMB
Page 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Page 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Page 29: ...Heat Pump SiBE12 519 20 Specifications ...
Page 135: ...Instruction SiBE12 519 126 System Configuration ...
Page 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...