Troubleshooting
SiBE12-519
154
Service Diagnosis
4.14
Position Sensor Abnormality
Remote
Controller
Display
H6
Method of
Malfunction
Detection
A compressor startup failure is detected by checking the compressor running condition through
the position detection circuit.
Malfunction
Decision
Conditions
The compressor is not running in about 15 seconds after the compressor run command
signal is sent.
Clearing condition: Continuous run for about 5 minutes (normal)
The system will be shut down if the error occurs 8 times.
Supposed
Causes
Compressor relay cable disconnected
Compressor itself defective
Outdoor unit PCB defective
Stop valve closed
Input voltage out of specification
Troubleshooting
Check No.13
Refer to P.177
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Reconnect as specified.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
(R3041)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Normal
NO
NO
NO
YES
YES
NO
YES
YES
Any LED off?
DC290~380V?
Electricals
or compressor harnesses
connected as
specified?
Check the electrolytic capacitor
voltage.
Check with the inverter checker (
∗
).
Turn off the power. Disconnect the
harnesses U, V and W.
C
heck No.
13
Check for short-circuit.
Summary of Contents for 2MKS40DVMB
Page 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Page 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Page 29: ...Heat Pump SiBE12 519 20 Specifications ...
Page 135: ...Instruction SiBE12 519 126 System Configuration ...
Page 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...