SiBE12-519
Troubleshooting
Service Diagnosis
149
4.11
Four Way Valve Abnormality
Remote
Controller
Display
EA
Method of
Malfunction
Detection
The liquid pipe temperature thermistor, the outdoor air temperature thermistor and the outdoor
unit heat exchanger thermistor are checked to see if they function within their normal ranges in
the operating mode.
Malfunction
Decision
Conditions
A following condition occurs after 3 minutes of the compressor start.
Cooling / dry operation
(outdoor unit heat exchanger temp. – liquid pipe temp.) < –5°C
Heating
(liquid pipe temp. – outdoor unit heat exchanger temp.) < 0°C
Supposed
Causes
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Four way valve coil or harness defective
Four way valve defective
Foreign substance mixed in refrigerant
Insufficient gas