CSV IP REPORTING NAME -
P201E 6E
The CSV reporting format allows for a name to be added to the beginning of the data. The name can be programmed
at this location and it applies to all monitoring addresses programmed at P203E 1-8.
CSV IP REPORTING PASSWORD -
P201E 7E
The CSV reporting format allows for a password to be added to the beginning of the data. The password field follows
the name field and can be programmed at this location and it applies to all monitoring addresses programmed at
P203E 1-8.
ALTERNATIVE GATEWAY
- P201E 8E
If the primary gateway was a land-based connection it is possible to set up a cellular back up (Alternative) Gateway
which the panel can revert to if the primary gateway is not working. If unused leave as 000.000.000.000. Do not
program an invalid secondary Gateway address as this will cause communications issues.
PRIMARY DNS SERVER
- P201E
9E
Monitoring addresses (P203E1-8E) and time servers (P201E11-12E) can be URL’s. The panel can find the IP
addresses by using this primary DNS server (Default: 8.8.8.8).
SECONDARY DNS SERVER
- P201E 10E
Monitoring addresses (P203E1-8E) and time servers (P201E11-12E) can be URL’s. The panel can find the IP
addresses by using this secondary DNS server (Default: 8.8.4.4)
PRIMARY TIME SERVER
- P201E 11E
If the panel is permanently connected to the internet the panel clock can be synced to an internet time server. The
primary time server can be programmed at this location. To allow the panel to sync to the internet time option 3 must
be turned on at address P201E4E and the correct time zone selected at P25E17E (Default NTP server:
0.nz.pool.ntp.org).
SERIAL OVER IP PORT
- P201E 13E
If option 4 is turned on at P201E4E the panel will allow TCP/IP communication with automation systems via the
Ethernet connection using the port programmed at this location. The default port number is 9000.
MONITORING IP REPORTING PORT NUMBER
- P204E 1-8E
There is a separate port number for each of the 8 IP Reporting Numbers
IP REPORTING POLL TIMER
- P202E 1-8E
There is a programmable poll timer for each of the possible 8 IP reporting numbers (P203E). The Poll timer can be
set to a value between 0-9999 minutes
.
MONITORING IP REPORTING NUMBER/URL
- P203E 1-8E
There are up to 8 IP Reporting Numbers/URL’s that can be programmed into the panel.
When entering in a URL at
the LCD keypad the letters (all lower case), and numbers, are entered in exactly the same way that LCD
text for zones, outputs, areas, etc, is entered. The number 1 key can be used to enter in a “1”, or “.” or “-”
in the URL or IP address.
MONITORING IP REPORTING PORT NUMBER
- P204E 1-8E
There is a separate port number for each of the 8 IP Reporting Numbers.