![Crow RUNNER 8/64 Installation & Programming Manual Download Page 92](http://html1.mh-extra.com/html/crow/runner-8-64/runner-8-64_installation-and-programming-manual_2689361092.webp)
Page 92
Access Control Options B
P6176E 1-64E
Access Control Options B
1 = Report access violation as output # not zone #
Page
(Default = None)
2 = Hide this zone on the web status page
3 = Zone restore auto-resets Egress outputs
Access Door Open Too Long Beeps to Keypads
P6177E 1-64E
Access Door Open Too Long Beeps to Keypads
Page
(Default = All Off)
01-32 = An Access Door left Open too long will Beep Keypad #1-32
Access Door Forced Open Beeps to Keypads
P6178E 1-64E
Access Door Forced Open Beeps to Keypads
Page
(Default = All Off)
01-32 = An Access Door forced Open twill Beep Keypad #1-32
Access Door Open Too Long to Outputs
P6179E 1-64E
Access Door Open Too Long to Outputs
Page
(Default = All Off)
01-32 = An Access Door left Open too long will trigger Output #1-32
Access Door Forced Open to Outputs
P6180E 1-64E
Access Door Forced Open to Outputs
Page
(Default = All Off)
01-32 = An Access Door forced Open twill trigger Output #1-32
+++++Time Zones+++++
Programming Holidays
P170E 1-32E
Holidays 1-32 Days -
Value = DDMMYY
Page 63
Programming Time Zone Days
P171E 1-32E
Time Zones 1-32 Days
Page 63
(Default = All Off)
1 = Sunday
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Invert
Programming Time Zone Start & End Times
P172E 1-32E
Time Zones 1-32 Start Time -
Value 0000-2359 (Default = 0000)
Page 63
P173E 1-32E
Time Zones 1-32 End Time -
Value 0000-2359 (Default = 0000)
Time Zone Options
P174E 1-32E
Time Zone 1-32 Options
Page 64
(Default = All Off)
1 = Ignore Holidays
2 = Dormant Time Zone (see P1032E)
+++++++++
Dialler Programming Options
P175E 1E
Dialler options
Page 64
(Default = 7)
1 = Dialler is Enabled
2 = Fax Defeat
3 = Disable Telephone Line Monitoring
4 = DTMF or Pulse Dial
(For DTMF, 4&5 must both be OFF)
5 = DTMF or Reverse Pulse Dial
(For DTMF, 4&5 must both be OFF)
6 = Send long DTMF tones during dialing
7 = Spare
8 = Spare
Dialler Programming Options 2
P175E 2E
Dialler options 2
Page 64
(Default = 1)
1 = Step number on each call
2 = Spare
3 = Spare
4 = Test calls only if armed
5 = Test Time Period is in days
6 = Hold line open following Domestic/Voice report for DTMF control
7 = Ring Timeout (Off = 3 secs, On = 6.5 secs).
8 = Answer After 1 ring for Listen-in Mode
Auto-Answer Ring Count
P175E 3E
Auto-Answer Ring Count -
Value 0-99 (Default = 25)
Page 65
Test Call Start Time
P175E 4E
Test Call Start Time -
Value 0000-2359 (Default = 2300)
Page 65