![Crow RUNNER 8/64 Installation & Programming Manual Download Page 50](http://html1.mh-extra.com/html/crow/runner-8-64/runner-8-64_installation-and-programming-manual_2689361050.webp)
Page 50
button disarm operation to work options 2 & 3 must be off at location P45E
KEYPAD <A> BUTTON AREA ASSIGNMENT
KEYPAD <A> BUTTON AREA ASSIGNMENT
- P78E 1-32E Value = 01-32 for Areas 1-32
Option 01
Area “1”
- This option assigns the keypad <A> button to Area 1. If a keypad <A> button is assigned to
only Area 1 it can only Arm or Disarm that area.
Option 32
Area “32”
- This option assigns the keypad <A> button to Area 32. If a keypad <A> button is
assigned to only Area 32 it can only Arm or Disarm that area.
KEYPAD <A> BUTTON AREA OPTIONS
KEYPAD <A> BUTTON AREA OPTIONS
- P79E 1-32E
Option 1 - <A> button can Arm
Option 2 - <A> button can Arm Stay Mode
Option 3 - <A> button can Disarm at All Times
Option 4 - <A> button can Disarm Stay Mode at All Times
Option 5 - <A> button can Reset Alarms
Option 6 - <A> button can Arm Latchkey Mode
Option 7 - <A> button can Disarm During Exit Delay
Option 8 - <A> button can Disarm Stay Mode During Exit Delay
Option 1
<A> button can Arm
- This option enables single button Arming using the <A> button. For single button
operation to work options 2 & 3 must be off at location P45E.
Option 2
<A> button can Arm Stay Mode
- This option enables single button Arming of Stay Mode using the
<A> button. For single button operation to work options 2 & 3 must be off at location P45E.
(NOTE: Following arming of Stay Mode, if the <ENTER> button is pressed, all entry & exit delays
will be reset to zero for that armed period).
Option 3
<A> button can Disarm at All Times
- This option enables single button Disarming using the <A>
button. For single button disarm operation to work options 2 & 3 must be off at location P45E
Option 4
<A> button can Disarm Stay Mode at All Times
- This option enables single button Disarming of Stay
Mode using the <A> button. For single button disarm operation to work options 2 & 3 must be off at
location P45E
Option 5
<A> button can Reset Alarms
- If this option is On, Pressing the <A> button (provided Option 3 is also
On) will reset an alarm condition without having to enter a user code.
Option 6
<A> button can Arm Latchkey Mode
- This option enables single button Arming of the alarm in
Latchkey report mode using the <A> button. For single button Arm operation to work options 2 & 3 must
be off at location P45E. When Latchkey Mode is set on Arming, any code without the Latchkey option
(P4E Option 6) used to Disarm the Alarm will cause a Disarm report to be sent via the dialler.
Option 7
<A> button can Disarm During Exit Delay
- This option allows single button Disarming using the <A>
button provided the Armed Mode exit delay is active. If the exit delay has expired the <A> button cannot
be used to disarm the alarm. For single button disarm operation to work options 2 & 3 must be off at
location P45E
Option 8
<A> button can Disarm Stay Mode During Exit Delay
- This option allows single button Disarming of
Stay Mode using the <A> button provided the Stay Mode exit delay is active. If the Stay Mode exit delay
has expired the <A> button cannot be used to disarm Stay Mode. For single button disarm operation to
work options 2 & 3 must be off at location P45E
KEYPAD <B> BUTTON AREA ASSIGNMENT
KEYPAD <B> BUTTON AREA ASSIGNMENT
- P80E 1-32E Value = 01-32 for Areas 1-32
Option 01
Area “1”
- This option assigns the keypad <B> button to Area 1. If a keypad <B> button is assigned to
only Area 1 it can only Arm or Disarm that area.
Option 32
Area “32”
- This option assigns the keypad <B> button to Area 32. If a keypad <B> button is