Reliability (103)
BACnetReliability
ENUMERATED: normal(0)
Vendor specific:
no response (64)
crc error (65)
exception, illegal function code (66)
exception, illegal data address (67)
exception, illegal data value (68)
exception, code+65, rarely used (69..79)
configuration property fault (80)
exception, code not recognized (81)
BACnet client read/write timeout (82)
BACnet client received error response from slave (83)
Out_Of_Service (81) (W)
BOOLEAN
COV_Increment (22) (W)
REAL (analog objects only)
Priority_Array (87)
BACnetPriorityArray (commandable objects only)
SEQUENCE SIZE (16) OF BACnetPriorityValue
REAL (each element, analog output objects)
ENUMERATED (each element, binary output objects)
Unsigned (each element, multi-state output objects)
Relinquish_Default (104)
(W)
REAL (analog objects)
ENUMERATED (binary objects)
Unsigned (multi-state objets)
Polarity (84)
BACnetPolarity (binary objects only)
ENUMERATED: normal(0)
Number_Of_States (74)
Unsigned (multi-state objects only)
Units (117)
BACnetEngineeringUnits (analog objects only)
Vendor Specific Object Properties:
Object_Map_Usage (801)
(W)
BIT STRING:
(0) object is mapped to BACnet object on another
device
(1) object is mapped to local physical I/O
(2) set default on power-up
(3) set default on comm. fail
(4) read periodic
(5) write periodic
(6) write on delta
(7) enable max quiet
(8) object value is persistent
(9) object is reserved for global use
12. Object Properties