3.4 Auto Connect
The fastest way to connect is to select the known baud rate, max master setting and
some unused local MAC. However, if you are connecting to a ValuPoint that has been
previously configured and you do not know its settings, you can use Auto Connect to
search for it. The Auto Connect does take some time because it is testing the various
possible baud rates. Then when it finds a baud rate that seems right, it spends some
time listening to polls for master to determine the max master setting that seems to
be in effect. It is also looking for an unused MAC (station ID) to use for the tool itself.
The tool will assign itself the highest numbered unused MAC address. Once a
seemingly good set of parameters is found, these will be inserted in the appropriate
windows for you, and you will see the indication ‘Auto connected’. You may now
proceed.
To auto connect, check Enable MS/TP via USB, then click the Auto Connect button. The
screen will initially look like this: