The Object column indicates the type and instance of BACnet object in the local
ValuPoint.
The R/W column indicates the following: R means periodic read, W means periodic
write, W+ means write on delta. RW+ means a combination of those, etc.
The Device column will show 'Local', or show what remote slave device this object is
mapped to. 'Local' means a physical I/O point on the local ValuPoint. ‘MS/TP[N]’
means BACnet slave whose device instance is N.
The Object column is significant only when the object is mapped via the MS/TP client
to a remote device. Object shows what object in the slave device is mapped to this
local object. The object type and instance are shown, e.g. ‘AI[1]’ means Analog Input
1.
Type shows the physical I/O point locally, or the remote object property type, such as
Present Value.
Present Value shows a representation of the present value of the BACnet object in the
ValuPoint.
Reliability code for the BACnet object in the ValuPoint is shown. These are listed in a
later section.
Status Flags shows the status flags for the object. The standard flags are: IN_ALARM,
FAULT, OVERRIDDEN, and OUT_OF_SERVICE respectively (i.e. last T/F is out of
service flag). The flag is F to show false/0 and T to show true/1.
11. View Data