1.3 Overview of the ValuPoint Devices
Control Solutions' ValuPoint® controllers are designed to be building blocks in a
distributed control system where controllers communicate peer to peer via BACnet
MS/TP. Each ValuPoint controller can access BACnet objects in other BACnet devices,
both ValuPoint controllers and other manufacturer’s devices. Remote objects are
mapped to local objects that mirror the value of the remote object. The ValuPoint®
Programmable I/O for BACnet MS/TP provides the standard profile BACnet Application
Specific Controller (B-ASC).
All of the ValuPoint features available to local objects are also available to the remote
mapped objects. This means the remote objects can be incorporated into the local
i.CanDrawIt® program.
The user has the ability to assign object allocation as part of setup of the controller.
Resources are allocated from a common pool, and the user has the ability to decrease
the number of one type of object in order to increase the number of another type.
Total object count will range from approximately 100 commandable objects (with full
priority array) to 200 read/write objects. Object types include analog, binary, and
multi-state variations of input, commandable output, and writeable value.
Model VP4-0630
ValuPoint VP4-0630 is a scaled down, low cost version of the VP4-2330 featuring 2
universal inputs that may be configured as analog or discrete, 2 dedicated discrete
inputs, and 2 Form A relay outputs.
Hardware Features of Model VP4-0630
• 2 Analog/universal inputs, software selectable types
• 0-10VDC, discrete, pulse count
• 10-bit A/D resolution
• Non-volatile totalizing count inputs
• 2 Discrete Inputs
• Dry contact closure to ground
• Pulse count (10Hz) capability
• Non-volatile totalizing count inputs
• 2 Discrete outputs
• Form A relay
• 2A @ 120VAC
• 2A @ 30VDC
• BACnet MS/TP at 9600 to 76800 baud
• Hardened RS-485 port
• 128KB non-volatile EEPROM configuration file capacity
• 64K Flash for User Program
• ARM 32-bit processor, 512K Flash, 56K RAM
• Powered by 18-30VDC or 24VAC 50/60 Hz