TRP1000-4450 Troposcatter C-Band Outdoor Amplifier
Revision 0
Serial-based Remote Product Management
5–29
MN-TRP1000-OD
Parameter
Type
Command
(Instruction
Code and
Qualifier)
Arguments
for
Command
or Response
to Query
Description of Arguments
(Note that all arguments are ASCII
numeric codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
Qualifier)
Response
to Query
(Target to
Controller)
Retrieve
Utility Status
N/A
23 bytes,
alpha-
numeric
Query only.
Used to Query the utility status of the unit.
Where:
ADR = the serial address
BDR = the serial baud rate
FMT = the serial format
VFD = the VFD brightness setting
RUS=
RUS?
RUS=x….x
(See
description
for details of
arguments)
Summary
Alarm Status
N/A
1 byte
Query only.
Indicates if there are any active alarm conditions.
SAS=x,
Where:
0 = no active alarms
1 = at least one active alarm
Example:
<1/SAS?
>0001/SAS=0’cr’’lf’
SAS=
SAS?
SAS=x
(See
description
for details of
arguments)
Remote Baud
Rate
SBR=
5 bytes
Command or Query.
Set remote baud rate as follows:
02400 = 2400 baud
04800 = 4800 baud
09600 = 9600 baud
19200 = 19200 baud
38400 = 38400 baud
Examples:
<0001/SBR=9600’cr’
>0001/SBR=’cr’’lf’
<0001/SBR?’cr’
>0001/SBR=09600’cr’’lf’
Note:
When changing baud rates remotely the response to
the command will be returned using the same baud
rate as that used to send the command.
Default Value: 09600
SBR=
SBR?
SBR*
SBR?
SBR=xxxxx
(Same
format as
command
arguments)