TRP1000-4450 Troposcatter C-Band Outdoor Amplifier
Revision 0
Serial-based Remote Product Management
5–11
MN-TRP1000-OD
Parameter
Type
Command
(Instruction
Code and
Qualifier)
Arguments
for
Command
or Response
to Query
Description of Arguments
(Note that all arguments are ASCII
numeric codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
Qualifier)
Response
to Query
(Target to
Controller)
Attenuation
ATT=
5 bytes
Command or Query.
Set the RF attenuation level from 0 to 10dB in 0.25dB steps.
Example:
<1/ATT=10.00’cr’
>0001/ATT=’cr’’lf’
Default Value:
10.00
Default ATT Step: 0.25 dB
ATT=
ATT?
ATT*
ATT?
ATT=xx.xx
(Same
format as
command
arguments)
Auxilliary
Mute
AUX=
1 byte
Command or Query.
Enable or disable the auxiliary mute hardware control.
Where:
1 = auxiliary mute enabled
0 = auxiliary mute disabled
Example:
<1/AUX=1’cr’
>0001/AUX=’cr’’lf’
Default Value:
0
AUX=
AUX?
AUX*
AUX?
Clear All
Stored
Alarms
CAA=
None
Command only.
Instructs the unit to clear all Stored Alarms. This command
takes no arguments.
Example:
<1/CAA=’cr’
>0001/CAA=’cr’’lf’
CAA=
CAA*
N/A
N/A
Clear All
Stored
Events
CAE=
None
Command only.
Clear all Stored Events. This command takes no arguments.
Example:
<1/CAE=’cr’
>0001/CAE=’cr’’lf’
CAE=
CAE*
N/A
N/A