ID-FLX Lite & Telecom Global Guide
176
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13656
Related applications
Description
The level for IL-NT-AIO plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO3 lev2
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13657
Related applications
Description
The level for IL-NT-AIO plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO4 lev2
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
5
-
Step
1
Comm object
13658
Related applications
Description
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
Note:
Plug-in analog inputs protection alarms can be configured following way.
AnlInAIO1 del
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...