ID-FLX Lite & Telecom Global Guide
225
9.2.8 IL-NT IO1 (optional card)
Plug-in into ID-Lite controller EXTENSION MODULE port.
Number of Analog outputs
4
Analog output range
0 to +VBatt ±1 V
Number of Binary inputs
4
9.2.9 IL-NT BIO8 (optional card)
Plug-in into ID-Lite controller EXTENSION MODULE port.
Number of Binary inputs/outputs
8 (configurable as input or output)
Maximal one Binary output current
0.4 A
Maximal total current per module
2.5 A
9.2.10 IGL-RA15 (Remote Annunciator)
Order code:
EM2IGLRABAA
EM2FPCRAEAA
Voltage supply
8-36 V DC
Consumption
0.35-0.1 A (+1 A max horn output), depends on supply voltage
Power supply
Operating temperature
-20 ˚C to +70 ˚C
Storage temperature
-30 ˚C to +80 ˚C
Protection front panel
IP65
Operating conditions
Dimensions
180 × 120 × 55 mm
Weight
950 g
Dimensions and weight
Maximum current
1 A
Maximum switching voltage
36 V DC
Horn output