ID-FLX Lite & Telecom Global Guide
35
5.1.2 Table of analog inputs options
LiteEdit
Modify
Possibility
Type
Not used
Alarm
Monitoring
Analog input isn’t used
Analog input is used for monitoring and protection
Analog input is used only for monitoring
Name
… text
Name in history
Up to 14 ASCII characters
Up to 4 ASCII characters for the name used in history records
Config
Analog
Binary
Tri state
ECU
Analog measuring in specified range.
Binary: open/close - threshold 750 Ω or 7 VDC (AIN6-AIN9)
Three (Triple)-state: open/close - threshold 750 Ω (only AIN1-AIN3), failure
<10 Ω or > 2400 Ω
Only for AIN1, 2 values are read from ECU unit
Alarm
properties
Direction
Under limit
Under step. Sensor fail does not activate protection.
Over limit
Overstep. Sensor fail does not activate protection.
UndFls
Under step and Sensor fail activates protection.
OvFls
Overstep and Sensor fail activates protection.
Window prot.
Combination of Under and Over protection at the same analog input
Type
Sensor fail
Warning
Wrn+Sd
CoolDown
Engine running
only
Check box: Alarms are valid only for running engines, if box is checked
Sensor
Sensor name
… text
Resulotion: number of decimal points
Dimension: bar, %, °C, etc.
Table and graph: customize curves
Contact type
NC
NO
Valid only for binary and three-state inputs
Valid only for binary and three-state inputs
Note:
User curves “Points” are adjustable in LiteEdit PC tool.
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...