State
Condition of the transition
Action
Next state
Not Ready
RPM < 2, Oil pressure not detected, D+ not
Active, no shutdown alarm active, other than OFF
mode selected
Ready
Prestart
1
Prestart time elapsed
STARTER on
FUEL SOLENOID on
2
MaxCrank time
counter started
Cranking
Cranking
1
RPM >Start RPM AND BI: Nominal/Idle is active
STARTER off
PRESTART off
Starting
RPM >Start RPM AND BI: Nominal/Idle is not
active
STARTER off
PRESTART off
READY TO LOAD on
Running
D+ input activated for 1 s or oil pressure detected
STARTER off
PRESTART off
Cranking
MaxCrank time elapsed, 1st attempt
STARTER off
FUEL SOLENOID off
STOP SOLENOID on
CrankFail pause timer
started
Crank pause
MaxCrank time elapsed, last attempt
STARTER off
PRESTART off
Shutdown (Start
fail)
Crank
pause
1
CrankFail pause elapsed
STARTER on
FUEL SOLENOID on
2
STOP SOLENOID off
MaxCrank time
counter started
Cranking
Starting
1
is active
FUEL SOLENOID on
2
STOP SOLENOID off
READY TO LOAD off
Starting
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Stop time elapsed or Engine s 10 s
elapsed
FUEL SOLENOID off
STOP SOLENOID on
Shutdown (Start
fail)
Running
Stop request
READY TO LOAD off
Cooling time timer
started
Cooling
is active
FUEL SOLENOID on
STOP SOLENOID off
READY TO LOAD off
Running
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...