ID-FLX Lite & Telecom Global Guide
134
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
10000
YES
Step
1
Comm object
11855
Related applications
Description
Load limit regulator PI output upper limit.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
LoadUpLimit
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
0
YES
Step
1
Comm object
11856
Related applications
Description
Load limit regulator PI output low limit.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
LoadDnLimit
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
-200.0 .. +200.0 [%]
Default value
0
YES
Step
0.1
Comm object
11857
Related applications
Description
This is setpoint is giving Load limit gain factor.
Load Gain
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...