ID-FLX Lite & Telecom Global Guide
119
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
ENABLED, CHRGFAIL, DISABLED [-]
Default value
DISABLED
-
Step
-
Comm object
9683
Related applications
Description
ENABLED
The D+ terminal is used for both functions - “running engine” detection and charge
fail detection.
CHRGFAIL
The D+ terminal is used for charge fail detection only.
DISABLED
The D+ terminal is not used. Default state.
Note:
The magnetization current is provided independently on this setpoint value.
The D+ charge fail protection becomes active after
reaches zero.
D+ function
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
ENABLED, DISABLED [-]
Default value
ENABLED
-
Step
-
Comm object
11086
Related applications
Description
The setpoint enables adjustment of the electronic engine control by following settings.
ENABLED
There is a full available control of an electronic engine given by the setting of the
ECU unit of the engine, i.e. Start request, Stop request, Speed request are enabled
if available. Default state.
DISABLED
Control of an electronic engine is fully blocked and the ID-Lite can only monitor the
values of an electronic engine.
ECU Control
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...