ID-FLX Lite & Telecom Global Guide
115
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
12
-
Step
1
Comm object
9097
Related applications
Description
Idle time delay starts when RPM exceeds
. Start fail is detected when during Idle
state RPM decreases below 2.
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes.
opens during Cooling period again.
Note:
Engine can be switched between Idle and Running state by
in MAN
mode.
Idle time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
..
[RPM]
Default value
800
-
Step
1
Comm object
9946
Related applications
Description
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by
and after Engine ShutDown.
Idle speed