ID-FLX Lite & Telecom Global Guide
111
Group: Engine parameters
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
5 .. 1500 [RPM]
Default value
350 RPM
-
Step
1
Comm object
9095
Related applications
Description
“Firing” speed when ID-Lite controller stops cranking (starter goes OFF).
Sd Underspeed protection is activated when RPM drops back below the Starting RPM for more than 5
second the engine starting procedure.
Note:
Limit is ignored when Gear teeth = 0 i.e. in engine operation without speed pickup (running state is
indicated from D+ or Starting POil.
Note:
Can appears during "Cranking state" i.e. Starter (or J1939 Start command) is activated then one
running condition was detected (D+ was activated or (POil > Starting POil) condition was filled) - i.e.
Starter was switched off based on previous condition and within time (Cranking time and fix 5 s)
minimum RPM does not appear (RPM > Starting RPM), then is activated RPM meas fail.
Starting RPM
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0.0 .. 100.0 [Bar]
Default value
4.5
-
Step
0.1
Comm object
9681
Related applications
Description
Controller stops cranking (starter goes OFF) when Oil Pressure (typically measured on AIN1) is over
Starting POil.
Note:
Oil Pressure can be also measured on binary sensor. Then is necessary adjust AIN1 as Binary
input and Starting POil=1.
Note:
There are three conditions for stop cranking:
(just in case the Gear
teeth > 0), StartingPOil and D+ (if enabled). Starter goes off when any of these conditions is valid.
Starting POil
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...