ID-FLX Lite & Telecom Global Guide
199
Related FW
2.5.0
Related applications
Comm object
36
Description
The output closes prior to the engine start (Prestart) and opens when
speed is
reached. During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Prestart
Related FW
2.5.0
Related applications
Comm object
574
Description
The output closes prior to the engine start and opens when
speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow or pre-heat.
Preglow
Related FW
2.5.0
Related applications
Comm object
40
Description
The output closes when engine starts and opens after
after stop of the engine.
Cooling pump
Related FW
2.5.0
Related applications
Comm object
Description
The output either follows the Nominal/Idle binary input or I/O button in MAN mode or follows the engine state
in AUT mode:
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to countdown
when Start speed reached. The
is not evaluated during idle time. Start fail
protection occurs if the RPM drop below 2RPM during idle state.
Note:
When LBI
is configured (to a physical binary input), it has priority and
the switching between the nominal and the idle speed by I/0 button is blocked.
Idle/Nominal
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...