Setpoint group
Sensors Spec
Related FW
2.5.0
Range [units]
[Always / Running / OFF]
Default value
OFF
-
Step
-
Comm object
14283
Related applications
Description
Setting of Counter 1 and Counter 2 mode:
Always
Corresponding counter counts pulses all time.
Running
Corresponding counter counts pulses only when engine is running.
OFF
Corresponding counter does not count pulses. Default settings.
Note:
The Total 1 and Total 2 values are visible in LiteEdit – Values – Statistics.
The Total 1 and Total 2 values disappear from controller screen when both Counter modes 1 and 2 are
switched OFF otherwise there is new screen between existing Statistics and Alarm list.
Counter mode 1, Counter mode 2
Group: AIO module
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13650
Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO1 lev1
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13651
Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO2 lev1
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...