![ComAp ID-Lite Global Manual Download Page 142](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907142.webp)
ID-FLX Lite & Telecom Global Guide
142
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
10
-
Step
1
Comm object
8377
Related applications
Description
Delay for ANALOG INPUT 3.
Note:
Analog input 3 is usually determined to Fuel Level measurement and it is resistive type of input
with range 0-2500 Ω.
AIN3 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
.. 40.0 [V]
Default value
36.0
-
Step
0.1
Comm object
9587
Related applications
Description
High battery voltage Warning limit.
Batt overvolt
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
80.0 ..
[-]
Default value
18.0
-
Step
0.1
Comm object
8387
Related applications
Description
Low battery voltage Warning limit.
Batt undervolt
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
5
-
Step
1
Comm object
8383
Related applications
Description
Delay for low and high battery voltage alarm.
Batt volt del
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...