ID-FLX Lite & Telecom Global Guide
197
Related FW
2.5.0
Related applications
Comm object
24
Description
Closed relay energizes the starter of engine.
The relay opens if:
The strating speed is reached or
Maximum time of cranking is exceeded or
Request to stop comes up
Starter
Related FW
2.5.0
Related applications
Comm object
22
Description
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
Cooled engine is stopped or
In pause between repeated starts
Fuel solenoid
Related FW
2.5.0
Related applications
Comm object
23
Description
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer; it stays active until all symptoms say the
engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure <
Note:
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact
the Stop solenoid can still be active (in that case it is deactivated before cranking).
Note:
In case when stop time period is lower than "stop engine detected" + 10 s, stop time period is
extended to this value due to safety reason. (stop engine detected = RPM<2, OilP not detected, D+ not
active)
Stop solenoid
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...