ID-FLX Lite & Telecom Global Guide
74
Events
specification
Protection
type
Information on binary
output available
195)
Description
Sd AIO
SD
YES
Shutdown alarm configurable on the
input of plug-in.
Binary input
Configurable
YES
Configurable Warning/Shutdown
alarms on the inputs of ID-Lite.
Battery flat
SD
YES
If the controller switches off during
starting sequence due to bad battery
condition it doesn’t try to start again
and activates this protection.
Start failed
SD
YES
Engine start failed.
RPM meas fail
SD
NO
At least one running condition was
detected (Poil>Starting POil or
energized D+) and do not appear
RPM>Starting RPM.
ParamFail
NONE
NO
Wrong checksum of parameters.
Happens typically after downloading
new firmware or changing of the
parameter. The controller stays in
INIT mode. Check all parameters,
write at least one new parameter.
Overspeed
SD
YES
The protection comes active if the
speed is greater than Overspeed
setpoint.
Underspeed
SD
YES
During starting of the engine when
the RPM reached the value of
Starting RPM setpoint the starter is
switched off and the speed of the
engine can drop under Start RPM
again. Then the Underspeed
protection becomes active.
Protection evaluation starts
5 seconds after reaching
StartingRPM.
EmergencyStop
SD
NO
If the input Emergency stop is
opened shutdown is immediately
activated.
PickupFault
SD
NO
Failure of magnetic pick-up sensor
for speed measurement.
Stop fail
SD
YES
Engine stop failed.
WrnServiceTime
WRN
NO
The period for servicing is set by the
NextServTime setpoint. The
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...