Value name
Short name
Dimension
Type
Frame name
Total Engine Hours
EngineHours
h
ANA
HR
Boost Pressure
Boost Press
bar
ANA
IC
Intake Manifold Temp
Intake Temp
°C
ANA
IC
If Cummins-Modbus x.x option is selected, following values are read from Modbus Register Data (for QSX15,
QSK45, QSK60):
Value name
Short name
Dimension
Type
Frame name
Red Shutdown Lamp
Red Lamp
-
BIN
10005
Yellow Warning Lamp
Yellow Lamp
-
BIN
10006
Engine Speed
RPM
RPM
ANA
30001
Coolant Temp
Coolant Temp
°C
ANA
30002
Oil Pressure (psig)
Oil Press
bar
ANA
30003
Oil Pressure (psia)
Oil Press
bar
ANA
30003
Running Time
Running Time
h
ANA
30008
Fuel Rate (UK)
Fuel
L/h
ANA
30018
Fuel Rate (US)
Fuel
L/h
ANA
30018
Intake Manifold Press
Intake Press
bar
ANA
30530
Intake Manifold Temp
Intake Temp
°C
ANA
30531
7.6 ECU Analog inputs
Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes, e.g.
measuring, displaying and alarm activation related to various quantities. The configuration thus allows using
nine analog inputs on the central unit and four analog inputs on plug-in module if connected.
If the engine without ECU is controlled by ID-Lite, the first analog input is permanently configured to Oil
Pressure, other analog inputs remain freely configurable.
7.7 Tier 4 engines support
When the configured ECU supports Tier4 standard, on the controller appears a supplementary screen where are
displayed the values relative to the Tier4.
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...