ID-FLX Lite & Telecom Global Guide
8
2 System overview
2.3 Configurability and monitoring
2.1 Warnings
ID-Lite controller can be remotely controlled. In case of the work on the engine check, that nobody can remotely
start the engine.
To be sure:
Disconnect remote control via RS232 line,
Disconnect input REM START/STOP or
Disconnect output STARTER
Note:
Because of large variety of ID-Lite parameters setting, it is not possible to describe all combination.
Some of ID-Lite functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or characteristic.
Note:
SW and HW must be compatible (e.g. ID-FLX Lite firmware and ID-FLX Lite hardware) otherwise the
function will be disabled. If wrong software is uploaded the message HARDWARE INCOMPATIBLE appears
on the controller screen.
In the case of using Boot load (jumper) programming – close Boot jumper, follow instruction in LiteEdit and
upload correct software.
2.2 General description
The key feature of ID-Lite is its easy-to-use operation and installation. Predefined configurations for typical
applications are available as well as user-defined configurations for special applications.
ID-Liteis a comprehensive controller for single engines with extended support of electronic engines and plug-in
modules.
ID-Lite controllers are equipped with a powerful graphic display showing icons, symbols and bar-graphs for
intuitive operation, which sets, together with high functionality, new standards in engine controls.
ID-Lite provides gas engine support without ventilation.
Controller supports WebSupervisor system. This system enables engine fleet and assets management as well
as pure monitoring. Visit
and
for more details about
WebSupervisor.
The key features are:
ECU support - for singlespeed and allspeed engines e.g. Cummins, Volvo, JohnDeer etc.
Flexibility - with our extension modules e.g. IL-NT AIO, IL-NT BIO8 etc.
Communication - via communication modules e.g. IL-NT-GPRS, IB-Lite, IL-NT-S-USB and PC tools Web
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...