4.4.4 IL-NT IO1
IL-NT IO1 is optional plug-in card. Through this card controller can drive up to 4 proportional valves and to use 4
additional binary inputs. The 0 V (GND) terminal is internally wired with battery minus internally, the 12-24 V
(+Ubat) terminal is wired to battery plus power supply of ID-Lite controller.
There should be, not more than 1 V, lower voltage compare to adjusted % of +Ubat voltage.
Note:
Analog output shorted to ground more than one second can damage the output circuit.