5.1.4 Current output transducers
ID-Lite analog inputs are mainly designed for resistor sensors
In special case transducers to 4-20 mA output can be used for oil measuring (10.0 Bar or 6.0 Bar). Use
predefined 4-20 mA / 100 or 4-20 mA / 60 sensors.
This method reduces the input resolution by less than 50%
Some types of transducers are not suitable for connection to ID-Lite analog inputs because of influencing by ID-
Lite analog input.
Default current sensor characteristic
Use with external resistor 120 Ω.
4-20 mA / 100
0-20 mA / 100
0-20 mA / (-20 to +120 °C)
Ω
Converted
Note 1 (*)
Note 2 (*)
Note 3 (*)
Note 4 (*)
120
0 mA
0 %
-20 °C
170
0
0 %
4 mA
20 %
8 °C
200
13
22 °C
230
25
25 %
8 mA
40 %
36 °C
280
38
50 °C
330
50
50 %
12 mA
60 %
64 °C
390
63
78 °C
460
75
75 %
16 mA
80 %
92 °C
560
88
106 °C
690
100
100 %
20 mA
100 %
120 °C
Note:
(*)
Note 1 - % range for 4-20 mA input
Note 2 - range 0-20 mA
Note 3 - % range for 0-20 mA input
Note 4 - characteristic 0-20 mA / (-20 to +120 °C)
5.1.5 Analog input extension measurement
On each analog input there is a possibility to connect voltage or current output sensor instead of resistive one.
Recommended wiring connection for these measurements are bellow.
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...