4.4.5 IL-NT BIO8
IL-NT BIO8 is optional plug-in card. Through this card controller can use up to 8 additional binary inputs or
outputs. At least one Batt- terminal has to be connected to battery minus power supply of InteliDrive controller,
if at least one binary output is configured. In case more than 4 binary outputs are configured is necessary to
connect both Batt- terminals.
4.5 Communication modules
4.5.1 IL-NT RS232
IL-NT RS232 is optional plug-in card, which enables ID-Lite controller for RS232 serial communication. This is
required for computer or Modbus connection. The card has to be inserted into the expansion “Communication
module” slot back on the controller, similarly to extension modules.