Troubleshooting
Chapter 6
750-177
6-5
WATER ON BASE
1. A cold environment and/or intermittent firing may allow inner casing to heat up
above the condensation temperature of the flue gasses.
A. Increase temperature of the cold boiler room if possible.
B. Verify insulation is in place between inner and outer casing and replace if
missing.
C. Reset controls for less cycling to allow boiler to run for longer periods of time
to heat inner casing above condensation temperature.
2. Cold system startup.
A. Any time a boiler is started with a cold system, it will produce condensate
until internal surface temperatures exceed 130
°
F. Internal condensation will
not be produced once a boiler has warmed up. Condensate will dry up after
a short time. Limit number of cold starts.
3. Cold return temperatures.
A. Return temperatures below 120
°
F. will continually produce condensation.
Raise return temperatures above 120
°
F.
4. Gasket leaks allow gases to escape and condence on relatively cool base.
A. Gasket may need to be replaced or inner casing not installer per instructions.
Install inner casing and gasket per instructions outlined in Chapter 8,
SectionD.
Problem
Solution
Summary of Contents for FLX 1000
Page 12: ...Chapter 1 General Description 1 6 750 177...
Page 68: ...Chapter 2 Profire V Burner 2 56 750 177...
Page 90: ...Chapter 4 Sequence of Operation 4 10 750 177...
Page 104: ...Chapter 5 Adjustment Procedures 5 14 750 177...
Page 110: ...Chapter 6 Troubleshooting 6 6 750 177...
Page 122: ...8 2 750 177 Figure 8 1 Typical Hot Water Flextube Casing...
Page 124: ...8 4 750 177 Figure 8 2 Typical Low Pressure Steam Flextube Casing...
Page 126: ...8 6 750 177 Figure 8 3 Typical High Pressure Steam Flextube Casing...
Page 128: ...Parts Chapter 8 8 8 750 177 Steam Pressure Controls...
Page 129: ...Chapter 8 Parts 750 177 8 9 Water Level Controls...
Page 130: ...Parts Chapter 8 8 10 750 177 Water Level Controls continued...
Page 131: ...Chapter 8 Parts 750 177 8 11 Water Column Main and Aux 15 Steam...
Page 132: ...Parts Chapter 8 8 12 750 177 Water Column Main and Aux 150 Steam...
Page 133: ...Chapter 8 Parts 750 177 8 13 Safety Valves...
Page 134: ...Parts Chapter 8 8 14 750 177...
Page 135: ......
Page 136: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...