PARALLEL POSITIONING
Combustion Air
Gas
Oil
COMPONENTS
DESCRIPTION
A two bladed damper is
controlled by an independent
parallel positioning actuator.
The remote mounted
modulating control
Safety shut off valve(s) are
provided to initiate the flow of gas.
The primary is a diaphragm or
motorized type valve which have
delayed opening rates to prevent
an “in rush” of gas. A butterfly type
gas metering valve is directly
coupled to a parallel positioning
actuator. A manually adjusted gas
regulator limits maximum firing
rate.
Pressure Atomization:
Two solenoid type safety
shut off oil valves initiate the flow of oil from the high
pressure pump to a return flow nozzle. In the return
line from the nozzle is an adjustable oil metering
valve which limits the amount of oil allowed to return
to the pump. The metering valve is direct coupled to
a parallel positioning actuator.
Operating Sequence
PRE-PURGE
From its closed position the damper is
driven open by a signal from the parallel
positioning control. The damper will
remain open for the duration of the pre-
purge cycle.
Valves are closed.
The pump is operational but the valves are
closed. Oil is flowing through an internal relief
valve and returning to the supply system.
STARTUP,
IGNITION
Damper returns to the low fire position in
preparation for startup.
Valves open. To prevent a surge the
primary gas valve opens at a slowed
rate. Gas flow to the manifold is metered
based on the butterfly valves low fire
setting.
Safety shut off valves open allowing oil to flow from
pump to nozzle. Oil pressure at the nozzle is based
on the pump's pressure setting less the volume of
oil returning through the metering valve.
RUN,
MODULATE
Damper is driven by its parallel
positioning actuator to a firing rate
position as determined by the parallel
positioning control. The actuator and
parallel positioning control will then
continue to adjust the damper and fuel
actuators position based on signals from
remote sensors until demand is satisfied.
The gas valves remain in their open
position. The metering valve and
actuator increases the flow of gas to the
manifold in conjunction with the opening
damper however, position adjustments
are made based on the fuel "curve"
stored in the parallel positioning control's
memory. The burner will continue to
modulate as described under the
combustion air heading until demand is
satisfied.
The safety shut-off oil valves remain open. The
metering valve and actuator decreases the flow of
oil returning to the pump in conjunction with the
opening damper however, position adjustments are
made based on the fuel "curve" stored in the parallel
positioning control's memory. This in turn is
increases the pressure and volume of oil at the
nozzle. The burner will continue to modulate as
described under the combustion air heading until
demand is satisfied.
SHUT DOWN,
POST-PURGE
Damper returns to its closed position
during or following post purge.
On shut down all gas valves close within
1 second. The butterfly valve returns to
it's starting position..
All valves immediately close. The metering valve
opens to it's low fire position. The oil pump is
operating with post-purge, but oil is flowing through
an internal relief valve and returning to the supply
system.
VARIATIONS
IC offers several parallel
positioning systems. Consult
the factory for types and
options.
None
On models with a simplex nozzle oil is
diverted from the supply line through the
meter and back to the pump before the first
safety shut-off valve.
Chapter 2
Profire V Burner
2-18
750-177
Summary of Contents for FLX 1000
Page 12: ...Chapter 1 General Description 1 6 750 177...
Page 68: ...Chapter 2 Profire V Burner 2 56 750 177...
Page 90: ...Chapter 4 Sequence of Operation 4 10 750 177...
Page 104: ...Chapter 5 Adjustment Procedures 5 14 750 177...
Page 110: ...Chapter 6 Troubleshooting 6 6 750 177...
Page 122: ...8 2 750 177 Figure 8 1 Typical Hot Water Flextube Casing...
Page 124: ...8 4 750 177 Figure 8 2 Typical Low Pressure Steam Flextube Casing...
Page 126: ...8 6 750 177 Figure 8 3 Typical High Pressure Steam Flextube Casing...
Page 128: ...Parts Chapter 8 8 8 750 177 Steam Pressure Controls...
Page 129: ...Chapter 8 Parts 750 177 8 9 Water Level Controls...
Page 130: ...Parts Chapter 8 8 10 750 177 Water Level Controls continued...
Page 131: ...Chapter 8 Parts 750 177 8 11 Water Column Main and Aux 15 Steam...
Page 132: ...Parts Chapter 8 8 12 750 177 Water Column Main and Aux 150 Steam...
Page 133: ...Chapter 8 Parts 750 177 8 13 Safety Valves...
Page 134: ...Parts Chapter 8 8 14 750 177...
Page 135: ......
Page 136: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...