Replacing a Power Filter Unit
Up to two -48 VDC Power Filter Unit (PFU) assemblies can be installed in the ASR 5000 chassis. Two PFUs
provide load-balancing and redundancy. The PFUs are located in the lower-rear of the chassis.
Although a single PFU can provide power for a fully loaded chassis, it is strongly recommended that two
PFUs always remain installed for load-balancing and redundancy.
Caution
During installation, maintenance, and/or removal, wear a grounding wrist strap to avoid ESD damage to
the components. Failure to do so could result in damage to sensitive electronic components and potentially
void your warranty.
Caution
This chapter provides instructions for replacing a PFU in the event of failure. It includes the following
sections:
•
Determining that a PFU has Failed, page 197
•
Removing the Failed PFU, page 198
•
Installing the Replacement PFU, page 200
•
What to do with the Failed PFU, page 203
Determining that a PFU has Failed
The chassis can use one of several mechanisms to indicate a PFU failure. The first indicator is when the
POWER LED on the PFU is off. If the LED is off and a starPowerState SNMP trap is generated with a value
of Failed (2), the PFU must be replaced.
If you do not receive this trap, try the following suggestions to diagnose the cause:
•
Verify that the power switch is in the ON position.
•
Verify that the RTN and -VDC lugs are attached according to the instructions provided in this document.
•
Verify that the ground lug is attached according to the instructions provided in this document.
•
Verify that the power source is on and is supplying the correct voltage and sufficient current.
ASR 5000 Installation Guide
197
Summary of Contents for ASR 5000
Page 16: ...ASR 5000 Installation Guide xvi About this Guide Contacting Customer Support ...
Page 64: ...ASR 5000 Installation Guide 48 Installation Procedure Overview Laser Notice ...
Page 100: ...ASR 5000 Installation Guide 84 Line Card Installation Installing the XGLC ...
Page 122: ...ASR 5000 Installation Guide 106 Cabling the Fast Ethernet 10 100 Line Card FLC2 Interfaces ...
Page 206: ...ASR 5000 Installation Guide 190 Removing and Installing SMC PC Cards Removing PC Cards ...
Page 212: ...ASR 5000 Installation Guide 196 Replacing the Chassis Air Filter Installing the Air Filter ...
Page 220: ...ASR 5000 Installation Guide 204 Replacing a Power Filter Unit What to do with the Failed PFU ...
Page 266: ...ASR 5000 Installation Guide 250 Safety Electrical and EMC Certifications Korean EMC ...
Page 270: ...ASR 5000 Installation Guide 254 Environmental Specifications Chassis Air Flow ...