NVF5 Series User Manual Chapter 6 Parameter Function Description
F6.02
Relay Output
Selection
16
0
~
63
F6.03
Reserve
--
--
F6.04
Output Terminal
Effective Status
Setting
(
HDO
、
RO
)
0x0000
0x0000
~
0x0003
F6.05
HDO Output Delay
Time
0.0s
(
0.0
~
3600.0
)
s
F6.06
HDO Output Setting
Selection
0.0s
(
0.0
~
3600.0
)
s
DO Terminal Function Description
:
Values
Function
Description
0
No Applicable
The terminals that are not used can be set to
"No Applicable" to prevent misoperation.
1
In Running Mode
Inverter is in Running mode, DO is effective.
2
Frequency Level
Detection Reach-FDT1
Refer to F6.14
、
F6.15 description
3
Frequency Level
Detection Reach -FDT2
Refer to F6.16
、
F6.17 description
4
Inverter Overload
Pre-Alarm
Inverter is in Overlaod status, DO is effective.
5
Under Voltage Status
Output
DC Bus voltage is lower than Under Voltage
Limit, DO is effective.LED indicates P.oFF
。
6
External Fault Stop
Inverter External Fault occurs and trip
fault“E.EF”
时,
DO is effective.
7
Reach Upper Limit
Frequency
Setting Frequency
≥Upper Limit Frequency,and
the running frequency reach the Upper Limit
Frequency
,
DO is effective.
8
Reach Lower Limit
Frequency
Setting Frequency
≤Lower Limit Frequency,and
the running frequency reach the Lower Limit
Frequency
,
DO is effective.
9
Zero Speed Running
Inverter runs and the output frequency is 0, DO
is effective.Inverter is in Stop Mode,DO is
ineffective.
10 ~ 11
Reserve
--
12
Simple PLC Step
Complete Indication
Simple PLC Step Complete, DO is effective.
13
PLC Recycle Complete
Simple PLC recycle completer
,
DO is effective.
15
Inverter Ready
If the output signal is effective, it means that the
inverter is fault-free, the DC Bus Voltage is
normal, the Disable Terminal of is ineffective,
and inverter can startst.
16
Fault Output
Inverter Fault, DO is effective.
17 ~ 18
Reserve
--
- 82 -