NVF5 Series User Manual Chapter 6 Parameter Function Description
6.11.1 Digital Input Setting
(
DI
)
NVF5 series has 5 mutifunctional Digital inputs
,
and HDI terminal can be used for
High Speed Pulse input
,
Terminal setting are as below
Code
Name
Default
Setting Range
Description
F5.01
DI1 Setting
1
0
~
63
See below
table
F5.02
DI 2 Setting
4
0
~
63
F5.03
DI 3 Setting
9
0
~
63
F5.04
DI 4 Setting
12
0
~
63
F5.05
HDI Setting
0
0
~
63
F5.06
Digital Input effective
status setting
0x0000
0x0000
~
0x001F
F5.07
DI filter time
0.010s
(
0.000
~
1.000
)
s
F5.10
DI 1 Delay Time
0.000s
(
0.000
~
60.000
)
s
F5.11
DI 2 Delay Time
0.000s
(
0.000
~
60.000
)
s
F5.12
DI 3 Delay Time
0.000s
(
0.000
~
60.000
)
s
F5.13
DI 4 Delay Time
0.000s
(
0.000
~
60.000
)
s
F5.14
HDI Delay Time
0.000s
(
0.000
~
60.000
)
s
DI Terminal Function Description
:
Values
Function
Description
0
No Applicable
The terminals that are not used can be set to "No
Applicable" to prevent misoperation.
1
Farward-FWD
Forward and Reverse operation set by external
digital inputs
2
Reverse-REV
3
Jog Forward
Program to jog running mode
,
Jogging frequency
、
jog Accel. Time set in parameter F8.00
~
F8.02
4
Jog Reverse
5
Three Wire Control
Program to three wire control mode
,
refer to “6.1
Start command setting”description
6
Clear Fault
Program to clear fault.Same as STOP key of
integral keypad
,
using this function can realize
remote fault clear
7
External Fault Input
Program to External Fault Input signal,easy to
monitor external device.After inverter receive
external fault signal
,
display“E.EF”-external device
fault
8
Reserve
--
9
Running Pause
When inverter is in decel. Stop mode, DI is ON,all
parameter setting(such as simple PLC
- 79 -