NVF5 Series User Manual
Appendix B Parameter list
Code
Name
Setting Range
Default
Change
Thousands Place
:
External
Fault-
E.EF
(
Same as ones
place
)
FE.39
Protection Selection2
in Fault Mode
0x0000 ~ 0x2222
Ones Place
:
Comm. Abnormal
-E.CE
0
:
Coast Stop
1
:
Stop per Stop Mode
2
:
Keep Running
Tens Place
:
Reserve
Hundreds Place
:
EEprom
Abnormal-E.EEP
0
:
Coast Stop
1
:
Stop per Stop Mode
Thousands Place
:
Reserve
0x0000
○
FE.40
Protection Selection3
in Fault Mode
0x0
000 ~ 0x2222
Ones Place
:
Load Loss-E.LL
0
:
Coast Stop
1
:
Decel. Stop
2
:
Keep Running by
Skipping to 7% Motor Rated
Frequency
,
Recover to setting
frequency when load recover
Tens Place
:
PID Feedback Loss
in Running Mode-E.FbL
0
:
Coast Stop
1
:
Stop per Stop Mode
2
:
Keep Running
Hundreds Place
:
Excessive
Speed Deviation
- E.dEv
(
Same
as tens place
)
Thousands Plac
:
Motor Over
Speed-E.OS
(
Same as tens
place
)
0x0000
○
FE.41
Protection Selection4
in Fault Mode
0x0000 ~ 0x2222
Ones Place
:
Reserve
Tens Place
:
Reserve
Hundreds Place
:
Reserve
Thousands Plac
:
Reserve
0x0000
○
FE.42
Protection Selection5
in Fault Mode
0x0000 ~ 0x2222
Ones Place
:
Reserve
Tens Place
:
Reserve
Hundreds Place
:
Reserve
0x0000
○
- 140 -