NVF5 Series User Manual
Chapter 6 Parameter Function Description
In this mode,DI3 is Run Enable input terminal
,
after Running command is given by
DI1
,
DI2 control the direction.As shown in the below figure
,
when SB1 is closed
,
when
pressing SB2 the inverter will start,when K is opened the inverter will run forward
,
when K
is closed the inverter will run reverse
;
when SB1 is opened the inverter will stop. In normal
Start and Running process
,
SB1 must be kept closed
,
SB2 will be took effect in rising
edge.
+24V
PLC
DI1
DI3
COM
SB2
DI2
SB1
K
K
RUN
0
1
Run
Forward
Run
Reverse
Figure 6-1-4 Three Wire Control Mode2
Paremeters Setting as below
:
Code
Name
Values
Description
F0.01
Command Channel
Selection
1
Terminal Control
F5.08
Terminal Control
Mode Selection
3
Three Wire Control Mode 2
F5.01
DI1 Function
Selection
1
Forward
(
“Enable”
)
F5.02
DI2 Function
Selection
2
Reverse
(
“FWD/REV
Switch”
)
F5.03
DI3
Function
Selection
5
Three Wire Control Mode
6.1.3 “Comm.”Setting Control
Set parameter F0.01=2
,
can realize Start
、
Stop command by Comm. control
NVF5 supports Modbus Communication mode. See Appendix A about Modbus
protocol description.
6.1.4 “Remote Keypad”Setting
Set parameter F0.01=3
,
when remote keypad is used
,
the inverter can be realized
RUN
、
STOP by remote keypad.When pressing RUN key,the inverter will start
,
RUN
indicator light
;
In running mode
,
press STOP key the inverter will stop
,
RUN indicator
light off.
- 41 -
Inverter