NVF5 Series User Manual
Appendix B Parameter list
Code
Name
Setting Range
Default
Change
F9.01
Feedback Selection
0
:
AI1
1
:
AI2
2
:
Reserve
3
:
AI1+AI2
4
:
AI1-AI2
5
:
MIN
(
AI1
,
AI2
)
6
:
MAX
(
AI1
,
AI2
)
7
:
HDI
8
:
Reserve
1
◎
F9.02
Reference Digital
Given Setting
(
0.0
~
100.0
)
%
50.0%
○
F9.03
KP
0.0
~
100.0
20.0
○
F9.04
Ki
0.01
~
10.00
2.00
○
F9.05
Kd
0.000
~
10.000
0.000
○
F9.06
Sampling Period
(
0.01 ~ 50.00
)
s
0.50s
○
F9.07
Reference Change
Time
(
0.00 ~ 650.00
)
s
0.00s
○
F9.08
Feedback Filter Time
(
0.00 ~ 60.00
)
s
0.00s
○
F9.09
PID Output Filter Time
(
0.00 ~ 60.00
)
s
0.00s
○
F9.10
Offset Limit
(
0.0 ~ 100.0
)
%
0.0%
○
F9.11
Differential limiting
(
0.00 ~ 100.00
)
%
0.10%
○
F9.12
The Max. Positive
Offset between the
Two Outputs
(
0.00 ~ 100.00
)
%
1.00%
○
F9.13
The Max. Negative
Offset between the
Two Outputs
(
0.00 ~ 100.00
)
%
1.00%
○
F9.14
Close Loop Output
Invert Selection
0
:
Close Loop Output is
Negative,Inverter Run in
Lower Limit Frequency
1
:
Close Loop Output is
Negative,Inverter Run Reverse
0
○
F9.15
Close Loop Adjust
0
:
Positive Direction
1
:
Negative Direction
0
◎
F9.16
Integral Adjustment
Selection
0x0000~0x0011
0
:
Ineffective
1
:
Effective
Ones Place
:
When Frequency
Reach
Upper/Lower
Limit,Integral Stop
Tens Place
:
When Frequency
Reach
Upper/Lower
Limit,Integral Continue
0x0000
○
F9.17
Kp2
0.0 ~ 100.0
20.0
○
- 129 -