![CHINT NVF5 Series User Instructions Download Page 134](http://html.mh-extra.com/html/chint/nvf5-series/nvf5-series_user-instructions_2602304134.webp)
NVF5 Series User Manual
Appendix B Parameter list
Code
Name
Setting Range
Default
Change
F9.18
Ki2
0.01 ~ 10.00
2.00
○
F9.19
Kd2
0 ~ 10.000
0.000
○
F9.20
Parameter Switch
Selection
0
:
Ineffective
1
:
DI Switch
2
:
Switch Automaticlly Based On
Offset
0
○
F9.21
Switch Offset 1
0.0% ~ F9.22
20.0%
○
F9.22
Switch Offset 2
F9.21 ~ 100.0 %
80.0%
○
F9.23
Close Loop Preset
Value
(
0.0 ~ 100.0
)
%
0.0%
○
F9.24
Preset Value Holding
Time
(
0.00 ~ 650.00
)
s
0.00s
◎
F9.25
Reference Feedback
Level
0 ~ 65535
1000
◎
F9.26
Feedback Loss
Detection Value
(
0.0 ~ 100.0
)
%
0.0%
◎
F9.27
Feedback
Loss
Detection Time
(
0.0 ~ 20.0
)
s
0.0
○
F9.28
Close Loop
Calculation Mode
0
:
No calculate when stop
1
:
Calculate when stop
0
○
F9.29
Close Loop
BackupsChannel
Selection
0
:
Digital Given
1
:
AI1
2
:
AI2
3
:
Reserve
4
:
HDI
0
○
FA Simple PLC and Multi-Preset Speed Control Group
FA.00
Simple PLC Running
Mode Selection
Range:0x0000 ~ 0x0112
Ones Place
:
PLC Running
Mode
0
:
Single Cycle then stop
1
:
Single Cycel then
holding the end valu
2
:
Continuous cycle
Tens Place
:
Store when Stop
0
:
No Store
1
:
Store stop step and
frequency
Hundreds Place
:
Store when
power off
0
:
No Store
1
:
Store stop step and
frequency
Thousands Place
:
Step Time
Unit Selection
0x0000
◎
- 130 -