![CHINT NVF5 Series User Instructions Download Page 39](http://html.mh-extra.com/html/chint/nvf5-series/nvf5-series_user-instructions_2602304039.webp)
NVF5 Series User Manual Chapter 5 Simple Parameter Menu and
Commissioning Process
F0.20
Parameter
Factory
Default
◎
0
:
No Effect
1
:
Fault Log Clear
2
:
Set to Factory Default
(
Except
Motor NP
Parameters and
Parameter F7.11
)
3
:
Reset Custom Parameter
Group to Factory Default
(
Except
Motor NP Parameters and
Parameter F7.11
)
4
:
All Parameter Reset to Factory
Default
5
:
Back Up Parameters
6
:
Using Back Up Parameters
7
:
Saving Back Up Parameters
Note
:
Only when you are using
backup parameters,backup
parameter are able to be
saved.Otherwise when power off
then re-power the inverter,except
the updated parameters other
parameters are always initial
value.
0
F2.00
Motor Type
○
0
:
AC Induction Motor
1
:
Reserve
2
:
Reserve
0
F2.01
Motor NP
Power
◎
(
0.1
~
1000.0
)
kW
Depend on
motor type
F2.02
Motor NP
Voltage
◎
0V
~
Inverter Rated Voltage
Depend on
motor type
F2.03
Motor NP
Current
◎
(
0.1
~
1000.0
)
A
Depend on
motor type
F2.04
Motor NP
Frequency
◎
0.01Hz ~ F0.07
Depend on
motor type
F2.05
Motor Poles
◎
2
~
24
4
F2.06
Motor NP
RPM
◎
(
0
~
60000
)
rpm
1430rpm
F2.22
Motor Auto
Tuning
◎
0
:
No Operation
1
:
Static Tune
2
:
Rotate Tune
0
- 35 -