NVF5 Series User Manual Chapter 6 Parameter Function Description
on Series
F8.07
Decel.Time 3
Depend
on Series
(
0.0
~
6500.0
)
s
-
F8.08
Accel. Time 4
Depend
on Series
(
0.0
~
6500.0
)
s
-
F8.09
Decel.Time 4
Depend
on Series
(
0.0
~
6500.0
)
s
-
F1.12
Accel./Decel.
Mode
Selection
0
0
~
2
0
:
Linear
Acceleration
1
:
S Curve
Acceleration1
2
:
S Curve
Acceleration2
F1.13
S-curve
Scale of
Starting Time
30.0%
(
0.0
~
100.0
)
%
-
F1.14
S-curve
Scale of
Stopping
Time
30.0%
(
0.0
~
100.0
)
%
-
6.4 Motor Auto Tuning
Motor auto tuning is a process which the inverter analyse motor parameters . The
auto tuning methods include static auto tuning and rotate auto tuning .
Code
Name
Default
Setting Range
Description
F2.22
Motor Auto
Tuning
0
0
~
2
0
:
No Operation
1
:
Static Tune
2
:
Rotate Tune
F2.00
Motor Type
0
0
~
2
0
:
AC Induction
Motor
1
:
Reserve
2
:
Reserve
F2.01
Motor NP
Power
Depend on
motor type
(
0.1
~
1000.0
)
kW
-
F2.02
Motor NP
Voltage
Depend on
motor type
0
~
Inverter Rated
Voltage
-
F2.03
Motor NP
Current
Depend on
motor type
(
0.01
~
1000.00
)
A
-
F2.04
Motor NP
Frequency
Depend on
motor type
0.01
~
F0.07
-
F2.05
Motor Poles
Depend on
motor type
2
~
24
-
- 62 -