NVF5 Series User Manual Chapter 6 Parameter Function Description
time, the output is effective.
,
Timer set by F8.33
35
AI1
〉
AI2
When AI1
〉
AI2
,
Output effective
36
Reserve
--
37
Current Running Time
Reach
When accumulate running time is exceed
F8.34- Current Running Reach Time
,
Output
effective.
6.11.3 Analog Input Function
(
AI
)
NVF5 Series has 2 Analog Input terminals -AI1
、
AI2
,
with -10V
~
+10V
、
4mA
~
20mA
,
AI2 can select V or mA signal by Dip switch on the PCB board.AI setting
mode,See Parameter“6.2.3 Analog Main Frequency Setting”.
6.11.4 Analog
、
Pulse Output Function
(
AO
、
HDO
)
NVF5 Series has 1 AO
,
1 High Speed Pulse Output(HDO).
Code
Name
Default
Setting Range
Description
F6.00 HDO Output Type
0
0
~
1
See Below
Table
F6.08
AO1 Output Setting
Selection
0
0
~
36
F6.09
HDO
Output Setting
Selection
0
0
~
36
F6.10
AO1 Zero Bias Correction
Factor
0.0%
(
-100.0
~
100.0
)
%
F6.11
AO1 Gain
1.00
-10.0.
~
10.00
F6.12 HDO Max. Output Pulse
Frequency
10.00kHz
(
0.01
~
100.00
)
kHz
AO
、
HDO Terminal Function Description
:
Values
Function
Description
0
No Applicable
No Applicable
1
Running Frequency
0
~
Max. Output Frequency
2
Setting Frequency
0
~
Max. Output Frequency
3
Ramp Reference
Frequency
0
~
Max. Output Frequency
4
Output RPM
0
~
Max. RPM
5
Output Current1
0
~
2 times Inverter Rated Current
6
Output Current 2
0
~
2 times Motor Rated Current
7
Output Torque
(
Absolute
)
0
~
3 times Motor Rated Torque
8
Output Power
0
~
2 2 times Motor Rated Power
9
Output Voltage
0
~
1.2 times Inverter Rated Voltage