Appendix B Parameter list
Code
Name
Setting Range
Default
Change
Starting frequency
F1.07
DC braking
wait time
(
0.0
~
100.0
)
s
0.0s
○
F1.08
DC braking
current
(
0.0
~
100.0
)
%
(
Rated
Current
)
0.0%
○
F1.09
DC braking time
(
0.00
~
100.0
)
s
0.0s
○
F1.10
Forward/Reverse
Deadband Time
(
0.0
~
300.0
)
s
0.0s
○
F1.11
Forward/Reverse
Switch Mode
0
:
Operating frequency lower
limit(F0.09) switching
1
:
Starting frequency(F1.01)
switching
0
○
F1.12
Accel. / Decel. Mode
Selection
0
:
Ramp Accel./Decel.
1
:
S curve Accel./Decel. 1
2
:
S curve Accel./Decel. 2
0
◎
F1.13
S-curve Scale of
Starting Time
(
0.0
~
100.0
)
%
30.0%
◎
F1.14
S-curve Scale of
Stopping Time
(
0.0
~
100.0
)
%
30.0%
◎
F2 Motor Parameter Group
F2.00
Motor Type
0
:
AC Induction Motor
1
:
Reserve
2
:
Reserve
0
◎
F2.01
Motor NP Power
(
0.1
~
1000.0
)
kW
Depend on
motor type
◎
F2.02
Motor NP Voltage
0V
~
Inverter Rated Voltage
Depend on
motor type
◎
F2.03
Motor NP Current
(
0.01
~
1000.00
)
A
Depend on
motor type
◎
F2.04
Motor NP Frequency
0.01Hz
~
Max. Output
Frequency F0.07
Depend on
motor type
◎
F2.05
Motor Poles
2
~
24
Depend on
motor type
◎
F2.06
Motor NP RPM
(
0
~
60000
)
rpm
1430
◎
F2.07
Motor Stator
Impedance
(
0.001
~
65.535
)
Ω
(
Inverter
Power <= 55kW
)
(
0.0001
~
6.5535
)
Ω
(
Inverter
Power > 55kW
)
Depend on
motor type
◎
F2.08
Motor Rotor Resistor
(
0.001
~
65.535
)
Ω
(
Inverter
Power <= 55kW
)
(
0.0001
~
6.5535
)
Ω
(
Inverter
Power > 55kW
)
Depend on
motor type
◎
F2.09
Motor Leakage
Inductance
(
0.01
~
655.35
)
mH
(
Inverter
Power <= 55kW
)
Depend on
motor type
◎
- 115 -