NVF5 Series User Manual Chapter 6 Parameter Function Description
10
DC Bus Voltage
(
0.0
~
1000.0
)
V
11
AI1
(
0
~
10
)
V
12
AI2
(
0
~
10
)
V
14
Pulse Input
(
0.01
~
100.00
)
kHz
18
Output Current
(
0
~
1000
)
A
19
Output Voltage
(
0
~
1000
)
V
20
Output Torque
(+
/
-)
-2 times Motor Rated Current
~
+
2
times Motor Rated Torque
6.12 Ride Through Function
The Ride Through function enables the system to run continuously during short time
power failure.
When a power failure occurs, inverter keeps in the Regenerative status, the DC Bus
Voltage is maintained in FE.16
,
avoid inverter stop due to short time input voltage cut off
to cause Undervoltage Fault.
Figure 6-12-1 Ride Through Function
Code
Name
Default
Setting Range
Description
FE.13
Instantaneous power
Off Action Selection
0
0
~
2
0
:
Ineffective
1
:
Decel.
2
:
Decel. Stop
FE.14
Judgement Voltage of
Instantaneous Action
90.0%
(
80.0
~
100.0
)
%
100% equals
Standard DC
Bus Voltage
FE.15
Judgement Time of
Instantaneous Power
Failure Voltage Rise
0.50s
(
0.00
~
100.00
)
s
-
- 85 -