3024-016c
King Edge
C-12
IRONER SPEED INTERLOCK ADJUSTMENT (IRN)
Adjustment Function
Range
(Increment)
Low Range
Select
High Range Select
Standard
Setting
IRON*
Sets the speed range of the
feeder discharge, in feet per
minute.
Minimum
000-048FPM
(4FPM)
NA
NA
28FPM
Maximum
052 - 180 FPM
(4 FPM)
152FPM
IPP*
Distance, in inches, flatwork
travels per pulse from the
ironer speed signal or
encoder.
.10” - 1.90”
(.02”)
Auto speed
erratic.
Auto speed erratic.
0.26 for encoder
1.00 for Century
1.84 for Imperial/
TriStar
FEEDER
PERCENT*
Determines the difference in
speed between the feeder to
the ironer.
70 - 98%
(2%)
Excessive pull
on flatwork
leads to
distortion.
Flatwork is crushed
in accordion
fashion.
98%
PWM
Determines source of the
controlling speed signal.
0 = Input - Feeder follows ironer speed (Auto).
1 = PWM - Feeder sets own speed (manual).
2 = Not used
0
* Only active when PWM=0. These parameters adjust the feeder speed automatically according to the ironer’s speed
signal or encoder.
Ironer Speed Interlock Adjustments
(IRN)
All of these settings deal with how the
spreader/feeder interacts with other machines in
the line from the viewpoint of speed control.
Settings include:
The unit’s minimum and maximum
speeds.
The distance traveled by the flatwork
between each ironer encoder pulse.
The feeder speed relative to the ironer.
Which machine in the line controls the
overall speed of the line.
When IRN is selected from the SELECT
ADJUSTMENT menu, the following displays:
IRON 028-152FPM 0.26IPP
FEEDER 90PERCENT PWM=0
•
•
•
•
IRON is actually two settings. The first number
set (3 digits after the word IRON), controls
the minimum speed at which the feeder can
operate.
The second set of IRON digits controls
the maximum speed at which the feeder can
operate. Combined together they set the min/max
operating range of the unit in feet per minute.
Also, notice that PWM has 3 possible settings.
Setting 0 allows the unit to operate in AUTO
mode with its speed controlled by the Chicago
®
ironer behind it.
Setting 1 allows the unit to operate in manual,
controlling its own speed. Setting 2 is no longer
used.
Refer to the table below for more information
about each available function to use as a guide
in making adjustments.
Summary of Contents for King Edge
Page 1: ...KING EDGETM Large Piece Spreader Feeder INSTRUCTION MANUAL...
Page 66: ......
Page 122: ......
Page 182: ......
Page 200: ......
Page 202: ......
Page 207: ...5 King Edge PL 3038 008M This Page Blank on Purpose...
Page 240: ...38 PL 3038 008M King Edge This Page Left Blank On Purpose...
Page 260: ...2...
Page 262: ...4...
Page 264: ...6...
Page 266: ...8 C...
Page 268: ...10...
Page 270: ...12...
Page 272: ...14...
Page 274: ...16...
Page 276: ...18...
Page 277: ...19...
Page 278: ...20...
Page 280: ...22...
Page 281: ...23...
Page 282: ...24...
Page 284: ...Skyline S1 S20 Installation...
Page 285: ......
Page 286: ...Skyline S1 S20 Installation...
Page 288: ......
Page 290: ......